Large commercial services are measured with transformer-rated meters. Current transformers (CTs), and at higher voltages potential transformers (PTs), step the service down so a standard meter can measure it. The meter's dial or register then records only a fraction of the real flow, and the billing system multiplies each reading by a constant to restore actual kWh and kW. For an 800:5 CT the multiplier is 160; with a 2:1 PT as well, it is 320. The multiplier lives in the utility's billing record, not on the meter face, so when a technician swaps a meter, upgrades CTs or changes the service, the record must be updated by hand. When it is not, every reading is scaled by the wrong number. The result is a step change in billed usage that does not match the building's operations, sometimes doubling the bill overnight. Under-billing happens too, and utilities can back-bill for it, so findings need care before filing.
How it happens
- CTs were replaced with a different ratio during a service upgrade and the billing record kept the old multiplier.
- A meter exchange moved from a self-contained meter to a transformer-rated meter, or the reverse, without a multiplier change.
- A meter with an internal multiplier was installed where the billing system applies an external one, scaling usage twice.
- kWh and kW (or kVARh) registers carry different multipliers in the billing record.
How to detect it
- Look for a step change in kWh or kW that coincides with a meter number change on the bill.
- Divide billed usage by the register difference to back out the multiplier the utility applied, and compare it to the CT and PT ratios on site.
- Compare billed demand to the service's physical capacity: billed demand above what the service can deliver points to a multiplier error.
- Check that consumption tracks occupancy, production volume or degree days before and after the change.
Evidence the utility will accept
- Bills before and after the meter or CT change, showing meter numbers and register reads
- Photographs of the CT nameplates and meter face showing ratio and any internal multiplier
- The utility's meter exchange or field work order
- Interval data showing the step change in recorded usage
Recovering the overcharge
We file a metering dispute with the nameplate photographs, register math and the work order date, and request a field verification of the CT ratio and multiplier. Once confirmed, utilities rebill every month since the change, usually within the back-billing limits of their tariff or state rules. These claims are among the fastest to resolve because the arithmetic is unambiguous once the ratio is verified on site.